NOTES:
1. IN FIGURE 1, THE TRANSMITTER IS CSA CERTIFIED FOR HAZARDOUS LOCATIONS, CLASS I, DIVISION 1, GROUPS C & D; CLASS II, DIVISION 1,
GROUPS E, F & G. THE PROBE IS INTRINSICALLY SAFE FOR CLASS I, DIVISION 1, GROUPS A, B, C & D; CLASS II, DIVISION 1, GROUPS E, F & G.
IN FIGURE 2, THE TRANSMITTER IS CSA CERTIFIED FOR ENCLOSURE 5. THE PROBE IS INTRINSICALLY SAFE FOR CLASS I, DIVISION 1,
GROUPS A, B, C & D; CLASS II, DIVISION 1, GROUPS E, F & G.
2. R. STAHL INC., MODEL 8901/33-293/000-79 OR CSA CERTIFIED EQUIVALENT (28.1V MAX., 300 OHM MIN.) POSITIVE-POTENTIAL SIGNAL RETURN
LINE BARRIER WITH INTRINSICALLY SAFE TERMINALS 2 (GROUND) AND 3. BARRIER MUST BE MOUNTED AND GROUNDED OUTSIDE THE
HAZARDOUS AREA IN ACCORDANCE WITH THE INSTRUCTIONS PACKED WITH BARRIER. POTENTIAL TO GROUND MUST NOT EXCEED 250V
RMS (360V PEAK).
3. ROBERTSHAW MODELS 158A – (A, B) (1, 2) – (C, D) 1.
4. ROBERTSHAW MODELS 158A – (A, B) (1, 2) – (A, B) 1.
5. ROBERTSHAW MODEL 702, 728, 729, 736, 738, 739, 740 0R 741 PROBE. INSULATED PROBES ONLY MAY BE USED IN CLASS II, GROUPS E & F
AREAS.
6. 650 OHMS MAXIMUM TOTAL LOOP RESISTANCE, EXCLUDING BARRIER RESISTANCE.
7. FOR AN INTRINSICALLY SAFE INSTALLATION, ALL WIRING BETWEEN THE BARRIER AND THE TRANSMITTER MUST BE INSTALLED IN RIGID
METAL CONDUIT.
DRAWING 907GA518
DIAGRAM FOR INTRINSICALLY SAFE
INTERCONNECTIONS FOR MODELS
158A-(A, B) (1, 2) - (A, B, C, D) 1
U.S.A. & Canada
Robertshaw Industrial Products
1602 Mustang Drive
Maryville, Tennessee 37801
Phone: (865) 981-3100 Fax: (865) 981-3168
http://www.robertshawindustrial.com
Exports
Invensys Controls
1701 Byrd Avenue
P.O. Box 26544
Richmond, Virginia 23261-6544
Phone: (804) 756-6500 Fax: (804) 756-6561
Comentários a estes Manuais